Analog meters with comparator
Applying |
One of the latest meter model produced by the Company is the electromeasuring meter with
the internal comparator.The meters are designed for the technological control and they are
used in the information boards.
Three types of meters are designed:
1. Single channel meter with one
operation threshold
2. Double channel meter with one
operation threshold per a channel.
3. Single channel meter with two
operation threshold for operation zone controlling.
Divider zone allows to set the operation threshold with the
accuracy of 2% in the range of 1-98% |
Inner block diagram of
M4264K, ÝÂ0704K |

|
MU - measuring unit
CU1, CU2 - comparing unit
LD - logical device
PS - power switch |
S - power source
Uref + D -reference voltage source and divider
I - indicator |
|
The meter has a power switch,
commutation current up to 100 mA for the external additional devices. |
External condition
diagram |
Conversion
type/
Contacts |
Meters
type |
1 channel
1 operation threshold |
2 channels
1 operation threshold per channel |
With operation zone
controlling |
1 |
OUT 1 (+) |
OUT 1 (+) |
OUT 1 (+) |
2 |
- |
OUT 2 (+) |
OUT 2 (+) |
3 |
- |
4 |
+ 24 V |
5 |
GNDA |
6 |
OUT 1 ( - ) |
7 |
|
OUT 2 ( - ) |
OUT 2 ( - ) |
|
Operating parameters |
Type
instrument |
Range of
measurement |
Loading
current
(Un=24V) |
Accuracy
class |
Overall
dimensions,
mass |
Operating
conditions |
Switch on
method |
M4264K

|
V 3-750 |
100 mA |
1,5 |
120x120x50 mm
0,35 kg |
Temperature
+5...+40 Ñ.
Relative humidity 90% at +30oÑ.
Vibration strength:
acceleration 5 m/s2
frequency 20 Hz.
Shock resistance:
acceleration 70m/s2
frequency 5...50/min. |
Direct |
V 1000-15000 |
With separated calibrated series resistor P4201 nominal current 5 mA |
mA
0,5-600
A 1-10 |
Direct |
A 20-750
kA 1-7,5 |
With the external calibrated shunt 75ØÈÑ and calibrated wires |
ÝÂ0702Ê

|
V 15-600 |
Direct |
450 V - 600 kV |
Through secondary winding voltage transformer 100 V |
|