ÝÊ0604 - Safety parameter of electrical installation of buildings
Purpose

Safety parameter meter of electrical installation of buildings ÝÊ0604 is a measuring means (GOST 22261) and it is designed to measure the parameters of the power network grounded the neutral and the parameters of the protective disconnection device (ÓÇÎ-Á) during acceptance (certification) tests of the electrical installation of the house and industrial buildings.

Properties

  • Designed on the base of monocristal microcomputer
  • Digital indication of measurement based on LCD indicator (16x4 symbols)
  • Spared mode of current effective value of the single-phase short circuit (pulse instantaneous current value is not more than 100A in the measuring circuit)
  • 120 measurement results being preserved and printed when power is switched- off
  • Remote control by means of the personal computer and information measuring system structure
  • Case protection degree in accordance with GOST 14254-IP30

Operating condition

  • Ambient air temperature:       from -10°C up to +40°C; 
  • Relative air humidity:    80% at  25° Ñ;
  • Atmospheric pressure:    84…106,7 kPa (630…800 mm Hg).

ÝÊ0604 measures

  • effective value of mains voltage (U)
  • network frequency (F)
  • current effective value of the single-phase short circuit (SC) to "ground" and "Z"
  • phase-shift between voltage and current of the single-phase short-circuit (j), and cosj
  • disconnecting differential current of the protective disconnection device (ID n)
  • disconnection time of the protective disconnection device (T)
  • direct-current resistance (R)
Measurement and error ranges
U= 50…300V d = ± 1% ID n = 30 mA  d = ± 4%
F = 45,00…55,00 Hz  d = ± 0,3% ID n = 100 mA d = ± 2%
ISC = 50…2000  A d = ± 10% ID n = 300 mA d = ± 2%
j = 1…30°   d = ± 10% ID n = 500 mA d = ± 2%
cos j = 1,0000…0,8660  d = ± 10% T = 0,010…10,000 s d = ± 0,3%
ID n = 6 mA  d = ± 10%  R = 0,100…1000 Om d = ± 1%
ID n = 10 mA d = ± 10%

Overall dimensions - 290x230x120 mm
Mass, not more - 3,8 kg
Power sorce - 220 V, 50 Hz

Power consumption - 50 VA
Mean-time-between - 10 yeares
Mean serice life - 2500 h